In this study, the cooling load of a housing unit in an apartment is calculated by TRNSYS program and compared with the cooling load data recommended by KS C 9306. The cooling load can be different from the estimation because the conditions of the housing unit vary with the building orientation, the location of the unit residence, balcony remodeling and the glazing size. To evaluate the influence of the building parameters on the cooling load, three types of housing unit are simulated with the parameters changed. It is concluded that the cooling load data of KS C 9306 overestimate the solar insolation, although most apartment buildings are protected from direct insolation by extruded balcony. The result of the simulation shows that solar insolation is critical to the cooling load of apartment building, especially in case of remodelling balcony into air conditioned area.