Ataei, Abtin (Graduate School of the Environment and Energy, Science and Research Branch, Islamic Azad University) Mirsaeed, Morteza Ghazi (Graduate School of the Environment and Energy, Science and Research Branch, Islamic Azad University) Choi, Jun-Ki (Department of Mechanical and Aerospace Engineering, University of Dayton) Lashkarboluki, Reza (Department of Chemical Engineering, Iran University of Science & Technology)
저널정보
테크노프레스 Advances in environmental research Advances in environmental research 제4권 제3호
발행연도
2015.1
수록면
155 - 172 (18page)

이용수

표지
📌
연구주제
📖
연구배경
🔬
연구방법
🏆
연구결과
AI에게 요청하기
추천
검색

초록· 키워드

오류제보하기
In this study, a complete set of recirculating cooling water system and the required instruments were built in a semi-industrial-scale and a 50 g/h ozone generation plant and a chlorine system were designed for cooling water treatment. Both chlorination and ozonation treatment methods were studied and the results were analyzed during two 45-days periods. The concentrations of ozone and chlorine in recirculating water were constant at 0.1 mg/lit and 0.6 mg/lit, respectively. In ozone treatment, by increasing the concentration cycle to 33%, the total water consumption decreased by 26% while 11.5% higher energy efficiency achieved thanks to a better elimination of bio-films. In case of Carbon Steel, the corrosion rate reached to 0.012 mm/yr and 0.025 mm/yr for the ozonation and chlorination processes, respectively. Furthermore, consumptions of the anti-corrosion and anti-sedimentation materials in the ozone cooling water treatment were reduced about 60% without using any oxidant and non-oxidant biocides. No significant changes in sediment load were seen in ozonation compared to chlorination. The Chemical Oxygen Demand of the blow-down in ozonation method decreased to one-sixth of that in the chlorination method. Moreover, the soluble iron and water turbidity in the ozonation method were reduced by 97.5% and 70%, respectively. Although no anaerobic bacteria were seen in the cooling water at the proper concentration range of ozone and chlorine, the aerobic bacteria in chlorine and ozone treatment methods were 900 and 200 CFU/ml, respectively. The results showed that the payback time for the ozone treatment is about 2.6 years.

목차

등록된 정보가 없습니다.

참고문헌 (0)

참고문헌 신청

함께 읽어보면 좋을 논문

논문 유사도에 따라 DBpia 가 추천하는 논문입니다. 함께 보면 좋을 연관 논문을 확인해보세요!

이 논문의 저자 정보

최근 본 자료

전체보기

댓글(0)

0