In this paper, we discussed the energy performance of underfloor air distribution(UFAD) and overhead air distribution(OA) system according to outdoor air flow rate in office building. The TRNSYS simulation was used for evaluation. The zone of the UFAD system was divided into two horizontal nodes to simulate the temperature stratification and the OA system was consisted of one zone considering full mixing in OA zone. Each node of UFAD system was coupled to its upper node. It is evaluating energy performance of each system according to 0CMH~500CMH outdoor air flow. In increase of outdoor air flow, UFAD system could reduce 12.4%-17.7% of summer energy and 19%~26% of spring/fall energy, And energy reduction rate of winter energy is not changed. It concluded that UFAD system is more effective in energy performance than the OA system accoring to outdoor air flow rate.