MITIGATION OF HIGH ENERGY ARCING FAULTS IN NUCLEAR POWER PLANT MEDIUM VOLTAGE SWITCHGEAR
Recommendations
Search

논문 기본 정보

Type
Academic journal
Author
Journal
Korean Nuclear Society Nuclear Engineering and Technology Nuclear Engineering and Technology 제51권 제1호 KCI Accredited Journals SCIE
Published
2019.1
Pages
317 - 324 (8page)

Usage

cover
MITIGATION OF HIGH ENERGY ARCING FAULTS IN NUCLEAR POWER PLANT MEDIUM VOLTAGE SWITCHGEAR
Ask AI
Recommendations
Search

Abstract· Keywords

Report Errors
A high energy arcing fault event occurred in the medium-voltage (13.8 kV and 4.16 kV) metalcladswitchgears in a nuclear power plant not only affecting switchgear but also connected equipment due tothe arc energy. The high energy arcing fault also causes a fire that influences the safety function of theunit. Therefore, from the safety point of view, it is necessary to evaluate the influences of high energyarcing fault events on the safety functions of nuclear power plants. The purpose of this paper is toelaborate the characteristics of high energy arcing faults and propose a high energy arcing fault mitigationscheme for medium voltage networks in nuclear power plants.