The present study has been conducted to explain control valve authority and solution for optimization of hydronics system. Part load condition makes distortion to characteristics of control valve due to decrease of pipe pressure drop and control valve authority. In order to maintain correct flow characteristic on control valve, differential pressure should be consistent and be applied to differential controller.