오류제보하기
This paper deals with assessment of potential interference between grounding electrodes using ETM(Electrolytic Tank Modeling) method. When a test current flowed through grounding electrode, potential rise was measured and analyzed using an electrolytic tank in real time. In order to analyze the potential interference between grounding electrodes, ETM method was studied. Potential interference between isolated grounding electrodes was evaluated as functions of the separation distance between grounding electrodes and the configuration of grounding electrode to be induced. It was found that the separation distance between grounding electrodes in reducing the potential interference was a major factor.