The heat transfer coefficient and pressure drop during gas cooling process of CO₂ (R-744) in inclined helical coil copper tubes were investigated experimentally. The main components of the refrigerant loop are a receiver, a variable-speed pump, a mass flow meter, a pre-heater and a inclined helical coil type gas cooler (test section). The test section consists of a smooth copper tube of 2.45 mm inner diameter. The refrigerant mass fluxes were varied from 200 to 600 [㎏/㎡s] and the inlet pressures of gas cooler were 7.5 to 10.0 [㎫]. The heat transfer coefficients of CO₂ in the inclined helical coil tubes increases with the increase of mass flux and gas cooling pressure of CO₂. The pressure drop of CO₂ in the gas cooler shows a relatively good agreement with those predicted by Ito’s correlation developed for single-phase in a helical coil tube. The local heat transfer coefficient of CO₂ agrees well with the correlation by Pitla et al. However, at the region near pseudo-critical temperature, the experiments indicate higher values than the Pitla et al. correlation. Therefore, various experiments in the inclined helical coil tubes have to be conducted and it is necessary to develop the reliable and accurate prediction determining the heat transfer and pressure drop of CO₂ in the inclined helical coil tubes.

목차

Abstract
1. 서론
2. 실험장치 및 방법
3. 냉각 열전달과 압력강하 특성
4. 결론
후기
참고문헌
저자소개

참고문헌 (13)

참고문헌 신청

함께 읽어보면 좋을 논문

논문 유사도에 따라 DBpia 가 추천하는 논문입니다. 함께 보면 좋을 연관 논문을 확인해보세요!

이 논문의 저자 정보

이 논문과 함께 이용한 논문

최근 본 자료

전체보기

댓글(0)

0

UCI(KEPA) : I410-ECN-0101-2009-559-015937523