In-situ measurement was made to evaluate chiller performance and thermal storage density of an ice thermal storage system. The system belonged to a big hotel and the measurement was conducted during late October. Owing to very small cooling load, the data logging was possible for a single thermal storage cycle. However, operation history of the chiller showed a relatively good spectrum of data for performance evaluation. COP and thermal storage density were calculated. The COP at full load was about 4.07, which was lower than 4.8~6.4 of new chillers. The measured storage density was about 10.9RT-h/㎥(=152 MJ/㎥), which also was lower than a criterion of normal performance (above 13.0 RT-h/㎥ or 181 MJ/㎥). The study result provides technical basis for quantitative ESCO business scenario.