An experimental investigation was made to study two-phase flow distribution in a T-type distributor of slit fin-and-tube heat exchanger using R-22. Experiments were carried out under the conditions of saturation temperature of 5℃ and mass flow rate varying from 0.6 to 1.2㎏/min. The inlet air has dry bulb temperature of 27℃, relative humidity of 50% and air velocity varying from 0.63 to 1.71㎧. A comparison was made between the predictions from the previously proposed tube-by-tube method and the present experimental data for the heat transfer rate of evaporator. Results show that 82.5% increase of air velocity is needed for T-type distributor with four outlet branches than that of two outlet branches under the superheat of 5℃, which resulted in increasing of air-side pressure drop of 130% for the former as compared to the latter.

목차

ABSTRACT

1. Introduction

2. Experiment

3. Simulation

4. Data reduction

5. Results and discussion

6. Conclusion

Appendix A

References