With possibility of hot water being able to be used as heating source in a liquid desiccant system, an experimental apparatus for regenerating was set up in a climate-controlled chamber and series of experiments were conducted. This study was performed to figure out an influence of experimental factors on regenerating performance and to suggest an optimal combination of factors affecting to regeneration rate. Furthermore, in order to find out the contribution ratio of factors on regenerating performance, a multi-way factorial design among design of experiments was adopted.
According to results, the most influential factor on regenerating performance was the temperature of liquid desiccant and the contribution ratio was about 79.4%. In addition, optimal combination for the best operating condition was 60℃ of solution temperature, 14 ℓ /min of solution flow rate, and 190㎥/h of air volume.